Application Macros
15-10
605 Series Frequency Inverter
Macro 4: Process PID
PID error derived from the difference of 2 analog inputs.
Digital input to disable PID.
Additional Operator Menu display parameters.
Terminal
Terminal
Terminal
Terminal
Name
Name
Name
Name
Purpose
Purpose
Purpose
Purpose
Comment
Comment
Comment
Comment
2
ANALOG INPUT 1
Process
Setpoint
0V = 0%, 10V = 100%
4
ANALOG INPUT 2
Process
Setpoint Trim
0V = 0%, 10V = 100%
5
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand, 0V = 0%,
10V = 100%
7
DIGITAL INPUT 1
Run
24V = Run
8
DIGITAL INPUT 2
Trip Reset
0V to 24V transition to reset trips.
9
DIGITAL INPUT 3
Direction
0V = Forward, 24V = Reverse
10
DIGITAL INPUT 4
External Trip
0V = Trip
11
DIGITAL INPUT 5
PID Enable
0V = PID Disabled, 24V = PID
Enabled
13
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
14
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The OPERATOR Menu for Macro 4
The default OPERATOR menu is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
PROCESS SETPOINT
STARTUP SCREEN
PROCESS FEEDBACK
PID ERROR
PID ENABLE
ENTER PASSWORD
Содержание 605 Series
Страница 16: ...1 4 Getting Started 605 Series Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605 Series Frequency Inverter ...
Страница 34: ...3 12 Installing the Inverter 605 Series Frequency Inverter ...
Страница 48: ...4 14 Operating the Inverter 605 Series Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605 Series Frequency Inverter ...
Страница 198: ...12 12 Certification for the Inverter 605 Series Frequency Inverter ...
Страница 202: ...13 4 Application Notes 605 Series Frequency Inverter ...
Страница 204: ...14 2 Serial Communications 605 Series Frequency Inverter ...