Parameter Specification Table
605 Series Frequency Inverter
Tag
(MMI) Name
Block
Type
Range
ID
Notes
267
RAMP SYM RATE
SYSTEM RAMP
INT
0.0 to 600.0 s
7f
268
RAMP SYM MODE
SYSTEM RAMP
BOOL
FALSE / TRUE
7g
269
COMMS SETPOINT
REFERENCE
INT
-300.00 to 300.00 %
7h
1, 4, 5
270
COMMS REF
COMMS CONTROL
BOOL
FALSE / TRUE
7i
Output
272
COMMS STATUS
COMMS CONTROL
WORD
0x0000 to 0xFFFF
7k
Output
273
COMMS COMMAND
COMMS CONTROL
WORD
0x0000 to 0xFFFF
7l
Output
274
HEALTHY
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7m
Output
275
FAST STOP LIMIT
STOP
INT
0.0 to 3000.0 s
7n
276
DRIVE ENABLE
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7o
277
/FAST STOP
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7p
278
/COAST STOP
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7q
279
RUN STOP MODE
STOP
ENUM
0 : RAMPED
1 : COAST
2 : DC INJECTION
7r
7
280
JOG
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7s
1
281
SEQ DIRECTION
LOCAL CONTROL
BOOL
FALSE / TRUE
7t
7
282
REM TRIP RESET
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7u
1
283
POWER UP START
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7v
284
STOP DELAY
STOP
INT
0.000 to 30.000 s
7w
285
RUNNING
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7x
Output
286
OUTPUT CONTACTOR
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7y
Output
287
READY
SEQUENCING LOGIC
BOOL
FALSE / TRUE
7z
Output
288
SWITCH ON ENABLE
SEQUENCING LOGIC
BOOL
FALSE / TRUE
80
Output
289
TRIPPED
SEQUENCING LOGIC
BOOL
FALSE / TRUE
81
Output
290
TRIP RST BY RUN
SEQUENCING LOGIC
BOOL
FALSE / TRUE
82
291
RUN FWD
SEQUENCING LOGIC
BOOL
FALSE / TRUE
83
1
292
RUN REV
SEQUENCING LOGIC
BOOL
FALSE / TRUE
84
1
293
/STOP
SEQUENCING LOGIC
BOOL
FALSE / TRUE
85
1
294
REMOTE REVERSE
SEQUENCING LOGIC
BOOL
FALSE / TRUE
86
295
COMMS SEQ
COMMS CONTROL
BOOL
FALSE / TRUE
87
Output
296
REMOTE REV OUT
SEQUENCING LOGIC
BOOL
FALSE / TRUE
88
Output
297
REMOTE SEQ
LOCAL CONTROL
BOOL
FALSE / TRUE
89
Output
298
SEQ MODES
LOCAL CONTROL
ENUM
Same as tag 265
8a
7
299
POWER UP MODE
LOCAL CONTROL
ENUM
0 : LOCAL
1 : REMOTE
2 : AUTOMATIC
8b
300
REMOTE COMMS SEL
COMMS CONTROL
BOOL
FALSE / TRUE
8c
7
301
MAIN SEQ STATE
SEQUENCING LOGIC
ENUM
0 : NOT READY
1 : START DISABLED
2 : START ENABLED
3 : SWITCHED ON
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
8d
Output
302
JOGGING
SEQUENCING LOGIC
BOOL
FALSE / TRUE
8e
Output
303
STOPPING
SEQUENCING LOGIC
BOOL
FALSE / TRUE
8f
Output
304
FAST STOP MODE
STOP
ENUM
0 : RAMPED
1 : COAST
8g
7
305
SYSTEM RESET
SEQUENCING LOGIC
BOOL
FALSE / TRUE
8h
Output
306
SWITCHED ON
SEQUENCING LOGIC
BOOL
FALSE / TRUE
8i
Output
307
REMOTE SEQ MODES
COMMS CONTROL
ENUM
0 : TERMINALS/COMMS
1 : TERMINALS ONLY
2 : COMMS ONLY
8j
7
308
REMOTE REF MODES
COMMS CONTROL
ENUM
Same as tag 307
8k
7
309
COMMS TIMEOUT
COMMS CONTROL
INT
0.0 to 600.0 s
8l
Содержание 605 Series
Страница 16: ...1 4 Getting Started 605 Series Frequency Inverter ...
Страница 22: ...2 6 An Overview of the Inverter 605 Series Frequency Inverter ...
Страница 34: ...3 12 Installing the Inverter 605 Series Frequency Inverter ...
Страница 48: ...4 14 Operating the Inverter 605 Series Frequency Inverter ...
Страница 156: ...8 2 Routine Maintenance and Repair 605 Series Frequency Inverter ...
Страница 198: ...12 12 Certification for the Inverter 605 Series Frequency Inverter ...
Страница 202: ...13 4 Application Notes 605 Series Frequency Inverter ...
Страница 204: ...14 2 Serial Communications 605 Series Frequency Inverter ...