3GS Technical Manual
Issue 4.5 August 2005
8-20 Programming Menus
Additional Information: Variables Table
Variable
Description
Default
min
max
Current Limit
Sets the power supply current limit in mA (0 to 9999) which when
exceeded, will generate an alert warning. For example, the limit for a 3A
PSU could be set to 2000mA, 3000mA for a 4A PSU, 5000mA for a 6A
PSU. When set to 0, PSU overcurrent will not be monitored.
0
0
9999
E/E Area 1-30
Sets the entry/exit time for the relevant Areas. Note: For Class IV compli-
ance the entry/exit time cannot exceed 45 seconds.
45
1
9999
E/E Common
Sets the entry/exit time for the Common area. The default is 45 seconds
for Class IV systems.
45
1
9999
Bell Delay
This is the delay period between an alarm digi-activation and the exter-
nal/area bell outputs being activated.
Note:
•
Setting this variable to 0 will disable all bells.
•The Maximum Bell Delay Period for EN50131 Compliance is 10 min-
utes (600 S)
•This Delay Period does not apply to System or Zone tampers.
1
0
9999
Bell Time
The time period for which the external siren/bell (output 2) and Com-
mon/Area bells will sound for before automatic shut down. For Class IV
Systems, the default bell time is 900 seconds. This setting can only be
changed if required to comply with local specifications. Setting this varia-
ble to 0 will give an infinite bell time.
900
0
9999
Modem
Set to YES if you want the modem to dial out on alarm. Compatible with
ED2000 or Eurodial 2000 PC software.
NO
NO
YES
Output Log
This variable controls the logging of outputs. If set to 1, any output which
changes state is logged. When set to 0, output activity is not logged.
When set to 2 outputs will not be logged when the System is being unset/
disarmed.
1
0
2
Arms
Set to YES if using the Arms Network system.
NO
NO
YES
Soak Test Days
The number of consecutive days for which a Soak Test is active.
14
0
9999
Service Reset
This facility is incorporated so that after an alarm activation, or any
tamper condition, a service company engineer must attend the installa-
tion and reset this variable to 1 before the System may be set/armed
again. An alarm in set/arm mode will increment the variable to 2 and
cause the message “+CALL ” to be displayed. If set to 0, then
a service visit is not required after an alarm activation.
Service Reset can be over-ridden by Coded Reset or by the engineer
accepting alerts – see Coded Reset in the
3GS Version 5 User Guide.
Note:
•For EN50131 compliance Service Reset variable must be set to 1.
•If DD243 variable is set to YES then a Service Reset will only be
required after a confirmed alarm.
1
0
2
Suspicion
Audible
If set to YES, an RPA Suspicion event will also cause the keypad to beep.
For use with a Radio PA handset.
NO
NO
YES
Содержание 3GS
Страница 4: ...Introduction iv...
Страница 12: ...Introduction 8...
Страница 14: ...1...
Страница 18: ...System Overview 1 6...
Страница 20: ......
Страница 22: ...Hardware Overview 2 4 SYSTEM CONFIGURATION The following diagram shows a typical configuration of the system...
Страница 26: ......
Страница 34: ......
Страница 38: ...Intelligent PSUs 4 6...
Страница 40: ......
Страница 97: ...Issue 4 5 August 2005 Nodes 5 59...
Страница 98: ...Issue 4 5 August 2005 Nodes 5 61...
Страница 100: ......
Страница 106: ...3GS Technical Manual...
Страница 116: ...3GS Technical Manual 7 12 Programming Overview Issue 4 5 August 2005 3GS Initial Setup Menu...
Страница 118: ...3GS Technical Manual...
Страница 146: ...3GS Technical Manual Issue 4 5 August 2005 Programming Menus 8 31 Node Configure Inputs Menu...
Страница 153: ...3GS Technical Manual Issue 4 5 August 2005 8 38 Programming Menus Service Mode Test Menu...
Страница 155: ...3GS Technical Manual Issue 4 5 August 2005 8 40 Programming Menus Service Mode Monitor Menu...
Страница 217: ...3GS Technical Manual Issue 4 5 August 2005 8 108 Programming Menus...
Страница 218: ...3GS Technical Manual Issue 4 5 August 2005 Programming Menus 8 109...
Страница 220: ......
Страница 222: ...3GS Version 5 User Guide 9 5 3GS SYSTEM KEYPAD DISPLAY...
Страница 254: ...3GS Version 5 User Guide 9 37 Some examples of Alert Messages...
Страница 262: ...3GS Version 5 User Guide 9 45 User name max 24 characters User no 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32...
Страница 264: ......
Страница 265: ...I n t h i s c h a p t e r HHT Overview 10 3 Main Menu 10 5 HAND HELD TERMINAL HHT 10...
Страница 266: ......
Страница 280: ......
Страница 288: ......
Страница 290: ......
Страница 293: ...Issue 4 5 August 2005 DM1200 Digital Communicator Modem 12 5...
Страница 301: ...I n t h i s c h a p t e r Network Router Overview 13 3 Sample Connection Diagram Scenarios 13 4 NETWORK ROUTER 13...
Страница 302: ......
Страница 304: ...Network Router 13 4 SAMPLE CONNECTION DIAGRAM SCENARIOS...
Страница 308: ...Network Router 13 8...
Страница 310: ......
Страница 316: ...IntelliBell 14 8 SELF ACTIVATING BELL To connect a Self Activating Bell SAB to the 3GS system see the following diagram...
Страница 318: ......
Страница 338: ...Issue 4 5 August 2005 Technical Specifications 15 23...
Страница 339: ...I n t h i s c h a p t e r 3GS Overview 16 5 Installing 3GS 16 6 Installing the Dongle 16 7 Upgrading 16 8 16 PC SOFTWARE...
Страница 340: ...1...
Страница 346: ......
Страница 366: ...17 22...
Страница 367: ...I n t h i s c h a p t e r Introduction to CiTeC II 18 3 CITEC II INSTALLATION 18...
Страница 368: ......
Страница 370: ...CiTeC II Installation 18 4...
Страница 377: ...Issue 4 5 August 2005 19 7...
Страница 378: ...19 8...
Страница 385: ......
Страница 386: ......