Issue 4.5 August 2005
Nodes 5-5
N
ODE
F
UNCTIONALITY
The following features are common to all nodes:
●
Ringnet Communications
●
Infrared Communication
●
On-Board Memory
●
On-Board Buzzer
●
Tamper Switches
Ringnet Communications
Europlex nodes are connected to each other via a two
wire RS485 network called the ringnet. It is wired in a
ring, starting from the 3GS controller to the first node,
and any subsequent nodes and, finally, from the last
node back to the controller. All nodes connect to the
ringnet in the same way and the same cabling conditions
apply. The maximum distance allowed from controller to
node is 500m if using Belden 9502 cable. A distance of
1000m is possible using UTP Category 5 solid core or
Belden 9829. The ringnet interface baud rate is 307KB.
Input/Output Functions
Each node has some input/output capabilities,
depending on the node. For the inputs to function as
3GS alarm zones, two 2K2 (US:1k and 470) end-of-line
resistors must be connected. The controller then
determines the zone status by reading the end-of-line
resistance value, according to the following table:
The outputs are 1Amp Form-C dry contact relay outputs.
These relays can be used to drive external devices, such
as a siren.
Infrared Communication
All nodes (except the RKD) are fitted with infrared
transmit and receive capability. This allows you to use the
3GS Hand Held Terminal (HHT) to program or
interrogate the system without having to make physical
connections, open boxes, and so on. You can
communicate with the system by simply switching on the
HHT and pointing it at the nearest node.
HHT gives access to node setup and status information,
such as:
●
Serial number
●
Software version fitted
●
Actual voltage and current used
●
Ringnet communications status
●
Status of inputs and their resistance values
●
Status of outputs
On-Board Memory
All nodes have on-board memory. This is used for storing
data, allowing you to program the system. Programming
can be done using:
●
the RKD
●
the HHT IR Link
●
a local or remote PC
See
3GS Programming
for further information.
On-Board Buzzer
Each node has its own piezo buzzer fitted, to allow you
to locate the node (for service and so on). You simply
have to locate the nearest node and request the missing
node to sound its buzzer, thereby highlighting its location
(for example, above false ceilings). You activate the
buzzer using the Node Find option. See
Node Configure-
>Information
in
3GS Programming
for further
information.
In addition, you can assign each node a text description
to help you locate it more easily.
Tamper Switches
All nodes monitor for front and back tampers. Some have
on-board tamper switches and some have terminals
supplied, depending on the cabinet. Most nodes allow
for bypassing tampers using on-board tamper links.
Note
The link must be removed to enable
tamper monitoring.
cable type
maximum
distance between
nodes
Belden 9502 (screened)
500m
UTP Category: 5 (solid core)
1000m
Belden 9829
1000m
description
value
zone status
OPEN
4400
Zone open
CLOSED
2200
Zone closed
DISCON
30 000
Zone disconnected
SHORT
< 1400
Zone shorted
DC SUBS
Variable
DC Voltage substitution
Содержание 3GS
Страница 4: ...Introduction iv...
Страница 12: ...Introduction 8...
Страница 14: ...1...
Страница 18: ...System Overview 1 6...
Страница 20: ......
Страница 22: ...Hardware Overview 2 4 SYSTEM CONFIGURATION The following diagram shows a typical configuration of the system...
Страница 26: ......
Страница 34: ......
Страница 38: ...Intelligent PSUs 4 6...
Страница 40: ......
Страница 97: ...Issue 4 5 August 2005 Nodes 5 59...
Страница 98: ...Issue 4 5 August 2005 Nodes 5 61...
Страница 100: ......
Страница 106: ...3GS Technical Manual...
Страница 116: ...3GS Technical Manual 7 12 Programming Overview Issue 4 5 August 2005 3GS Initial Setup Menu...
Страница 118: ...3GS Technical Manual...
Страница 146: ...3GS Technical Manual Issue 4 5 August 2005 Programming Menus 8 31 Node Configure Inputs Menu...
Страница 153: ...3GS Technical Manual Issue 4 5 August 2005 8 38 Programming Menus Service Mode Test Menu...
Страница 155: ...3GS Technical Manual Issue 4 5 August 2005 8 40 Programming Menus Service Mode Monitor Menu...
Страница 217: ...3GS Technical Manual Issue 4 5 August 2005 8 108 Programming Menus...
Страница 218: ...3GS Technical Manual Issue 4 5 August 2005 Programming Menus 8 109...
Страница 220: ......
Страница 222: ...3GS Version 5 User Guide 9 5 3GS SYSTEM KEYPAD DISPLAY...
Страница 254: ...3GS Version 5 User Guide 9 37 Some examples of Alert Messages...
Страница 262: ...3GS Version 5 User Guide 9 45 User name max 24 characters User no 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32...
Страница 264: ......
Страница 265: ...I n t h i s c h a p t e r HHT Overview 10 3 Main Menu 10 5 HAND HELD TERMINAL HHT 10...
Страница 266: ......
Страница 280: ......
Страница 288: ......
Страница 290: ......
Страница 293: ...Issue 4 5 August 2005 DM1200 Digital Communicator Modem 12 5...
Страница 301: ...I n t h i s c h a p t e r Network Router Overview 13 3 Sample Connection Diagram Scenarios 13 4 NETWORK ROUTER 13...
Страница 302: ......
Страница 304: ...Network Router 13 4 SAMPLE CONNECTION DIAGRAM SCENARIOS...
Страница 308: ...Network Router 13 8...
Страница 310: ......
Страница 316: ...IntelliBell 14 8 SELF ACTIVATING BELL To connect a Self Activating Bell SAB to the 3GS system see the following diagram...
Страница 318: ......
Страница 338: ...Issue 4 5 August 2005 Technical Specifications 15 23...
Страница 339: ...I n t h i s c h a p t e r 3GS Overview 16 5 Installing 3GS 16 6 Installing the Dongle 16 7 Upgrading 16 8 16 PC SOFTWARE...
Страница 340: ...1...
Страница 346: ......
Страница 366: ...17 22...
Страница 367: ...I n t h i s c h a p t e r Introduction to CiTeC II 18 3 CITEC II INSTALLATION 18...
Страница 368: ......
Страница 370: ...CiTeC II Installation 18 4...
Страница 377: ...Issue 4 5 August 2005 19 7...
Страница 378: ...19 8...
Страница 385: ......
Страница 386: ......