900-00275-01-001 Rev A
49
Operation
Battery Tab
The items under this tab affect the Mojave inverter’s interactions with the battery bank, particularly
battery charging.
Many items will vary with the battery type. There are no default settings that apply to all batteries.
Each
Battery Model
selection pre-loads the other items with default settings that have been
optimized for that particular battery type. The default settings shown below are those used for the
Custom Lead Acid
selection.
NOTE:
If the Mojave ESS battery is in use, refer to the
Mojave Energy Storage System
Operator’s Manual
in place of the present manual. This manual, also called the
ESS
Manual
, contains necessary battery and inverter instructions. The
ESS Manual
also
includes inverter presets for the Mojave ESS battery.
The items presented here are described on the designated pages. They may not appear in the
same order as shown below.
Battery Model
— All supported battery models, with preloaded specifications. See page 51. As noted,
the settings here are for the
Custom Lead Acid
selection.
Amp hours per string (Ah)
— Range:
0
to
2000
. Default:
200
.
The size (amp-hours) of each “string”, or set of batteries in series. See page 51.
Number of strings
—
1
to
100
. Default:
1
.
The number of battery strings in parallel with each other. See page 51.
Max SOC (%)
— Range:
60
to
100
. Default:
100
.
The uppermost SOC for the charger to work. See page 52.
Min SOC (%)
— Range:
10
to
60
. Default:
50
.
The lowest operating point for the inverter. See page 52.
Max charge current (A)
— Range:
0
to
175
. Default:
170
The maximum total charging current that is permitted to charge the battery bank by any means.
See page 53.
Max discharge current (A)
— Range:
0
to
200
. Default:
170
The maximum total DC current that is permitted to discharge the battery bank by any means.
See page 53.
Rebulk voltage (V)
— Range:
40
to
64
. Default:
48.00
The trigger voltage to re-start a charging cycle. See pages 59 and page 68.
Absorb charge mode
— Range:
Disabled
or
Timed
. Default:
Timed
The command that permits the second stage of charging to operate. See pages 57 and 67.
Absorb voltage (V)
— Range:
40
to
64
. Default:
56.5
The target voltage for the first two stages of charging. See pages 57 and 67.
Absorb time (m)
— Range:
0
to
1439
. Default:
120
The duration for the second stage of charging. See pages 57 and 67.
Absorb end amps (A)
— Range:
0.2
to
170
. Default:
4.0
7
7
Содержание OutBack POWER Mojave OGHI8048A
Страница 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Страница 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Страница 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Страница 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Страница 114: ...114 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Index This page intentionally left blank...
Страница 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...
Страница 116: ...900 00275 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...