900-00275-01-001 Rev A
47
Operation
NOTES:
The charger cannot exceed the
Import limit (W)
setting, even if
Charge from grid limit
is set higher than
Import limit (W)
.
The inverter gives priority to any loads. The inverter cannot restrict the amount of
power sent to the loads.
If the combination of loads and charging exceeds
Import limit (W)
, the inverter will
reduce the charge rate to avoid overloading the source. This could cause the
inverter to charge at a rate considerably less than the
Grid charge limit
setting.
If the loads
equal
Import limit (W)
, the charge rate will be reduced to zero.
If the loads
exceed
Import limit (W)
, see below.
The
Charge from grid limit (W)
setting does not restrict charging performed while AC
coupling. See page 39.
Demand Mitigation (Peak Reduction)
If the loads exceed
Import limit (W)
, the inverter will support the loads by adding battery power to
the power used from the grid. It will discharge the batteries at a level up to the
Max Discharge
Current (A)
setting on page 53.
This operation can continue until the batteries reach the
Minimum SoC
setting on page 52.
IMPORTANT:
With sustained loads and no other DC source, the batteries may discharge to the
Low
Battery Cut-Out
point. The inverter will shut down with an error message. (See pages 19
and 52.) To prevent the loss of power, load use should be planned accordingly.
Содержание OutBack POWER Mojave OGHI8048A
Страница 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Страница 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Страница 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Страница 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Страница 114: ...114 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Index This page intentionally left blank...
Страница 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...
Страница 116: ...900 00275 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...