900-00275-01-001 Rev A
73
Operation
If the loads exceed
Generator output rating (kVA)
, the inverter will support the loads by adding battery
power to the power used from the generator. It will discharge the batteries at a level up to the
Max
Discharge Current (A)
setting on page 53.
This operation can continue until the batteries reach the
Minimum SoC
setting on page 52.
IMPORTANT:
With sustained loads and no other DC source, the batteries may discharge to the
Low
Battery Cut-Out
point. The inverter will shut down with an error message. (See pages 19
and 52.) To prevent the loss of power, load use should be planned accordingly.
Generator Relay
The Mojave inverter uses mechanical relays to alternate between the states of inverting and of
accepting an AC source. The
G
RID
and
G
EN
terminals have separate, independent relays.
These terminals are not interchangeable. Each input has a separate set of acceptance criteria.
Until the generator relay energizes, the
G
EN
terminals are electrically isolated from
L
OAD
. When
the relay closes, the
G
EN
and
L
OAD
terminals are electrically common. (The
G
RID
terminals remain
isolated.) When the relay changes states, the physical transfer delay is as fast as 20 milliseconds.
The inverter’s input is limited to 55 Aac per phase or line. The continuous loads should never
exceed this. When connected to an AC source, the inverter cannot limit the load current. The
G
EN
or
L
OAD
circuit breakers may trip.
CAUTION: Equipment Damage
Current draw in excess of the recommended amount can damage the inverter’s components.
This damage is not covered by warranty. Use protective devices of appropriate size.
IMPORTANT:
Do
not apply generator
power to the
G
RID
terminals.
Do not apply grid power to the
G
EN
terminals.
NOTES:
The neutral connections are not switched. Neutral conductors use a common bus bar.
The independent inputs are intended to simplify the connection to multiple AC sources;
however, the inverter can only use one input at a time. If both inputs are powered, the
default setting is for the inverter to accept the
G
RID
input.
If the generator’s voltage or frequency vary too widely, the inverter will disconnect itself.
However, any variations within the inverter’s acceptance range will be transferred to
the loads
.
The inverter does not “clean up” or condition the power from the source.
Содержание OutBack POWER Mojave OGHI8048A
Страница 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Страница 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Страница 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Страница 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Страница 114: ...114 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Index This page intentionally left blank...
Страница 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...
Страница 116: ...900 00275 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...