Operation
The exit (taper) current level for the second stage of charging. See pages 57 and 67.
Refloat voltage (V)
— Range:
42
to
64
. Default:
50.00
The trigger voltage to re-start a maintenance charge. See page 58.
Float charge mode
— Range:
Disabled
,
Timed
,
Continuous
. Default:
Timed
The command that permits the third stage of charging to operate. See page 58.
Float voltage (V)
— Range:
40
to
64
. Default:
54.5
The target voltage for the third (maintenance) stage of charging. See page 58.
Float time (m)
— Range:
0
to
1439
. Default:
120
The duration for the third stage of charging. See page 58.
Equalize voltage (V)
— Range:
40
to
64
. Default:
56.5
The target voltage for an equalization cycle. See page 62.
Equalize time (m)
— Range:
0
to
1439
. Default:
0
The duration for an equalization cycle. See page 62.
HBCO (V)
— Range:
40
to
64
. Default:
60.00
The voltage setting for high battery cut-out. See page 52.
HBCI (V)
— Range:
40
to
64
. Default:
58.00
The recovery point for HBCO. See page 52.
HBCO delay (s)
— Range:
0
to
1
. Default:
1.0
The delay for HBCO to take effect. See page 52.
LBCO (V)
— Range:
40
to
64
. Default:
44.00
The voltage setting for low battery cut-out. See page 52.
LBCI (V)
— Range:
40
to
64
. Default:
44.50
The recovery point for LBCO. See page 52.
LBCO delay (s)
— Range:
0
to
10
. Default:
10
The delay for LBCO to take effect. See page 52.
Temperature compensation (mV/C)
— Range:
0
to
10
. Default:
5.0
The amount (“slope”) that the battery charging is adjusted for temperature changes. This adjustment is
made in millivolts per degree Celsius per battery cell. See page 63.
Charge efficiency
— Range:
50
to
100
. Default:
95
The efficiency factor which modifies the final battery state of charge. See page 63.
Содержание OutBack POWER Mojave OGHI8048A
Страница 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Страница 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Страница 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Страница 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Страница 114: ...114 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Index This page intentionally left blank...
Страница 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...
Страница 116: ...900 00275 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...