900-00275-01-001 Rev A
67
Operation
Bulk Stage
This is the first stage in the cycle. It is a constant-current stage which drives the battery voltage up.
Bulk typically leaves the batteries at 75% to 90% of their capacity, depending on the battery type,
the exact charger setting, and other conditions.
Displayed
:
Status message: Bulk
Voltage Used:
Absorb voltage (V)
setting.
Exiting to Absorption stage:
Upon reaching the
Absorb voltage (V)
setting.
The DC current will operate at a high level, often as high as the charger’s maximum. The actual
charging kilowatts are shown in Figure 34.
Figure 34 Absorption Stage
Absorption Stage
This is a timed constant-voltage stage. It uses only enough current to maintain the Absorb voltage
(usually requiring a tapering current). It "tops off" the batteries at effectively 100% SoC.
Displayed
:
Status message: Absorb
Voltage Used:
Absorb voltage (V)
setting. For the three-stage cycle to proceed
normally, this setting should be kept higher than the
Rebulk voltage (V)
setting.
Exiting to Idle:
Upon reaching the
Absorb time (m)
or
Absorb end amps (A)
setting.
Содержание OutBack POWER Mojave OGHI8048A
Страница 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Страница 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Страница 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Страница 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Страница 114: ...114 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Index This page intentionally left blank...
Страница 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...
Страница 116: ...900 00275 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...