900-00275-01-001 Rev A
107
Specifications
Table 10
Grid Protection Settings (HECO and ISO-NE)
Range of
Adjustment
Certified
Range
HECO 14H-2018
ISO NE-2018
ISO NE-2021
Parameter
Min
Max
Min
Max
Volt/VAr
7
Disabled
Enabled
n/a
n/a
Enabled Disabled Disabled
Volt/VAr Vref (pu)
0.950
1.050
n/a
n/a
1
1
1
Volt/Var Vref Auto
Disabled Enabled
n/a
n/a
Disabled Disabled Disabled
Volt/VAr auto vref
response time (s)
300 5000
n/a
n/a
300
300
300
Volt/VAr response
time (s)
0.0 90.0
n/a
n/a
10.0
5.0
5.0
Volt/VAr 1 voltage (pu)
0.770
1.050
0.770
1.030
0.940
0.920
0.920
Volt/VAr 1 reactive
power (pu)
0.000 0.700
0.000
0.530
0.440
0.440
0.440
Volt/VAr 2 voltage (pu)
0.920
1.050
0.920
1.050
0.970
0.980
0.980
Volt/VAr 2 reactive
power (pu)
–0.700 0.700
–0.530
0.530
0.000
0.000
0.000
Volt/VAr 3 voltage (pu)
0.950
1.080
0.950
1.080
1.030
1.020
1.020
Volt/VAr 3 reactive
power (pu)
–0.700 0.700
–0.530
0.530
0.000
0.000
0.000
Volt/VAr 4 voltage (pu)
0.950
1.230
0.970
1.180
1.060
1.080
1.080
Volt/VAr 4 reactive
power (pu)
–0.700 0.000
–0.530
0.000
–0.440
–0.440
–0.440
Volt/Watt Disabled
Enabled
n/a
n/a
Disabled Disabled Disabled
Volt/Watt response
time (s)
0.0 90.0
n/a
n/a
10.0
10.0
10.0
Volt/Watt 1 voltage (pu)
1.000
1.090
1.000
1.090
1.060
1.060
1.060
Volt/Watt 1 power (pu)
1.000
1.000
1.000
1.000
1.000
1.000
1.000
Volt/Watt 2 voltage (pu)
1.010
1.100
1.010
1.100
1.100
1.100
1.100
Volt/Watt 2 power (pu)
–1.000
1.000
0.000
0.000
–1.000
0.000
0.000
LV1 voltage (pu)
0.000
0.980
0.500
0.950
0.880
0.880
0.880
LV1 time (s)
0.08
50.00
0.100
50.00
21.00
2.00
3.00
LV2 voltage (pu)
0.000
0.980
0.250
0.700
0.700
0.500
0.500
LV2 time (s)
0.08
50.00
0.10
50.00
11.00
1.10
1.10
LV3 voltage (pu)
0.000
0.980
0.250
0.700
0.500
n/a
n/a
LV3 time (s)
0.08
50.00
0.10
50.00
2.00
n/a
n/a
LV momentary
voltage (pu)
0.000 0.980
n/a
n/a
0.500
0.500
0.500
LV momentary time (s)
0.08
50.00
n/a
n/a
0.16
0.08
0.08
HV1 voltage (pu)
1.020
1.200
1.050
1.200
1.100
1.100
1.100
HV1 time (s)
0.08
13.00
0.10
13.00
1.00
2.00
2.00
HV2 voltage (pu)
1.020
1.200
1.050
1.200
1.200
1.200
1.200
HV2 time (s)
0.08
13.00
0.10
13.00
0.16
0.16
0.16
HV momentary
voltage (pu)
1.020 1.200
n/a
n/a
n/a n/a
1.100
HV momentary time (s)
0.08
13.00
n/a
n/a
n/a n/a
0.08
LF1 Hz (Hz)
50.00
59.98
50.00
59.9
57.00 58.50 58.50
LF1 time (s)
0.16
1000.00
0.16
1000.00
21.00
300.00
300
LF2 Hz (Hz)
50.00
59.98
50.00
59.9
56.00
56.50
56.50
LF2 time (s)
0.16
1000.00
0.16
1000.00
0.16
0.16
0.16
7
Only one of the four VAr functions (
Volt/VAr
,
Watt/VAr
,
Constant PF
,
Constant VAr
) can be enabled at one time.
Содержание OutBack POWER Mojave OGHI8048A
Страница 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Страница 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Страница 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Страница 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Страница 114: ...114 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Index This page intentionally left blank...
Страница 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...
Страница 116: ...900 00275 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...