Proline Promass F 300 EtherNet/IP
Diagnostics and troubleshooting
211
12.11 Event logbook
12.11.1 Reading out the event logbook
A chronological overview of the event messages that have occurred is provided in the
Events list
submenu.
Navigation path
Diagnostics
menu →
Event logbook
submenu → Event list
F
I1091 Config. change
I1157 Mem.err. ev.list
F311 Electr. failure
/ ../Eventlist
0d01h19m10s
A0014008-EN
29
Taking the example of the local display
• A maximum of 20 event messages can be displayed in chronological order.
• If the
Extended HistoROM
application package (order option) is enabled in the device,
the event list can contain up to 100 entries .
The event history includes entries for:
• Information events → 212
In addition to the operation time of its occurrence, each event is also assigned a symbol
that indicates whether the event has occurred or is ended:
• Diagnostic event
– : Occurrence of the event
– : End of the event
• Information event
: Occurrence of the event
To call up the measures to rectify a diagnostic event:
• Via local display → 191
• Via "FieldCare" operating tool → 194
• Via "DeviceCare" operating tool → 194
For filtering the displayed event messages → 211
12.11.2 Filtering the event logbook
Using the
Filter options
parameter you can define which category of event message is
displayed in the
Events list
submenu.
Navigation path
Diagnostics → Event logbook → Filter options
Filter categories
• All
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
• Information (I)