Commissioning
Proline Promass F 300 EtherNet/IP
140
10.5.13 Configuring the partial filled pipe detection
The
Partial filled pipe detection
wizard guides you systematically through all parameters
that have to be set for configuring the monitoring of the pipe filling.
Navigation
"Setup" menu → Partially filled pipe detection
‣
Partially filled pipe detection
Assign process variable
Low value partial filled pipe detection
High value partial filled pipe detection
Response time part. filled pipe detect.
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign process variable
–
Select process variable for
partially filled pipe detection.
• Off
• Density
• Reference density
Off
Low value partial filled pipe
detection
One of the following options is
selected in the
Assign process
variable
parameter
(→ 140):
• Density
• Reference density
Enter lower limit value for
deactivating partialy filled pipe
detection.
Signed floating-point
number
200
High value partial filled pipe
detection
One of the following options is
selected in the
Assign process
variable
parameter
(→ 140):
• Density
• Reference density
Enter upper limit value for
deactivating partialy filled pipe
detection.
Signed floating-point
number
6
000
Response time part. filled pipe
detect.
One of the following options is
selected in the
Assign process
variable
parameter
(→ 140):
• Density
• Reference density
Enter time before diagnostic
message is displayed for
partially filled pipe detection.
0 to 100 s
1 s
Содержание Proline Promass F 300
Страница 148: ...Commissioning Proline Promass F 300 EtherNet IP 148 Separator 158 Backlight 158...
Страница 263: ......