Commissioning
Proline Promass F 300 EtherNet/IP
112
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Current span
–
Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
• Fixed current
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
0/4 mA value
One of the following options is
selected in the
Current span
parameter (→ 112):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Enter 4 mA value.
Signed floating-point
number
Country-specific:
• 0 kg/h
• 0 lb/min
20 mA value
One of the following options is
selected in the
Current span
parameter (→ 112):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Enter 20 mA value.
Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current
The
Fixed current
option is
selected in the
Current span
parameter (→ 112).
Defines the fixed output
current.
0 to 22.5 mA
22.5 mA
Damping output 1 to n
One of the following options is
selected in the
Assign current
output
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Density
• Reference density
• Concentration
• Temperature
• Carrier pipe temperature
• Electronic temperature
• Oscillation frequency 0
• Oscillation amplitude 0
• Frequency fluctuation 0
• Oscillation damping
fluctuation 0
• Tube damping fluctuation 0
• Signal asymmetry
• Exciter current 0
Detailed description of
the options
Oscillation
frequency, Oscillation
amplitude, Oscillation
damping
and
Signal
asymmetry
:
Value 1
display
parameter
One of the following options is
selected in the
Current span
parameter (→ 112):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Set reaction time for output
signal to fluctuations in the
measured value.
0.0 to 999.9 s
1.0 s