Proline Promass F 300 EtherNet/IP
Diagnostics and troubleshooting
203
Diagnostic information
Remedy instructions
Coding of diagnostic
information (hex)
No.
Short text
443 Pulse output 1 to n
1. Check process
2. Check pulse output settings
• 0x800008C
• 0x8000121
Status signal
S
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Coding of diagnostic
information (hex)
No.
Short text
444 Current input 1 to n
1. Check process
2. Check current input settings
0x80001EB
Status signal
S
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Coding of diagnostic
information (hex)
No.
Short text
453 Flow override
Deactivate flow override
0x2000094
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Coding of diagnostic
information (hex)
No.
Short text
484 Failure mode simulation
Deactivate simulation
0x2000090
Status signal
C
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Coding of diagnostic
information (hex)
No.
Short text
485 Measured variable simulation
Deactivate simulation
0x2000093
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Coding of diagnostic
information (hex)
No.
Short text
486 Current input 1 to n simulation
Deactivate simulation
0x20001EC
Status signal
C
Diagnostic behavior
Warning