![Endress+Hauser Liquiline Control CDC90 Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/endress-hauser/liquiline-control-cdc90/liquiline-control-cdc90_operating-instructions-manual_2407406079.webp)
Liquiline Control CDC90
Operation
Hauser
79
Pump
The pumps are activated via the
System Settings
menu. The pilot valves are configured
here.
Path:Menu/System Settings/Pump
Function
Options
Info
Pump type
Factory setting
Pneumatic
Pneumatic or electric
Pilot valve Slot
Factory setting
1
Enter the slot of the pilot valves here if you have
more than one.
Valve for pump 1 ...3
Factory setting
5...7
Pumps 1 to 3 start on this valve.
Relay pump 1 ...3
Factory setting
1...3
Pumps 1 to 3 start on this relay.
Conveyed volume pump 1 ...3
Factory setting
100 ml/s
Specify delivery volume of pump 1 to 3 in ml/s
Delivery head
Factory setting
5 m
Specify delivery head of pump in m.
Calibration
With the
Calibration
button it is possible to
determine the delivery volume of the pump
Info: Fill canister 1 with 5 liters of water.
Canister
Path:Menu/System Settings/Canister
Function
Options
Info
Used canister 1...3
Enter via text box
Confirm if this canister is being used.
Expiration date
Enter via text box
Use-by date of liquid. Please follow the
manufacturer's specifications.
Batch
Enter via text box
Label on nameplate of liquid.
Value
Enter via text box
Buffer value of liquid
Manufacturer
Enter via text box
Manufacturer specification
Initial volume can. 1 ...3
Factory setting
5 liters
Actual volume of canisters.
Digital inputs
Options
• CM44 DIO
• Remote DIO
•
Factory setting
CM44 DIO
Select DIO module of control unit
Input Level can. 1 ...3
Factory setting
1...3
Configuration of float switches. The inputs in the
DIO for the level values are specified here.
Pilot valves
Path:Menu/System Settings/Pilot Valve Bloc
Function
Options
Info
Pilot valve Slot
Enter via text box
Select slot in pilot valve manifold
Number of valves
Enter via text box
Number of valves in slot
Start Position
Enter via text box
Position of slot in pilot valve manifold
Control of process valves
Enter via text box
Control unit in pharmaceutical sector
Содержание Liquiline Control CDC90
Страница 2: ......
Страница 117: ...Liquiline Control CDC90 Index Endress Hauser 117 Warnings 5 Water pipe 27 Web browser 59 Web server 54 111 Weight 113 ...