Description of parameters
Hauser
103
EDITOR TABLE (770)
Options
Select the function for the editor table.
Options:
• Next point: enter next point.
• Last input point: jump back to previous point to correct a mistake for example.
• Accept input table: save editor table as measuring table. This overwrites the old
measuring table.
• Abort: save values entered up to this point for the editor table and display next
parameter. The editor table is not activated as a measuring table.
• Insert point: see example below.
• Delete point: the current point is deleted. See example below.
Example:
Add point, in this case between the 4th and 5th point for example
– Select point 5 via the EDITOR TABLE/LINE NUMB parameter.
– Confirm current X and Y values with Enter.
– Using the TABLE EDITOR (770) parameter, select the option "Insert point".
– Point 5 is displayed for the TABLE EDITOR/LINE NUMB parameter. New values for
the X-VAL and Y-VAL parameters.
Example:
delete point, in this case the 5th point for example
– Select point 5 via the EDITOR TABLE/LINE NUMB parameter.
– Using the TABLE EDITOR (770) parameter, select the option "Delete point".
– The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Factory setting:
Next point
MEASURING TABLE (549)
Display
A point of the linearisation table saved (measuring table) appears on the display
The parameter first displays the first point of the linearisation table. By entering a line
number, you can directly display the corresponding point in the linearisation table.
MEASURING TABLE (717)
Selection
Select the function for the measuring table.
Options:
• Next point: view next point of the measuring table.
• Last input point: view previous point of the measuring table.
• Abort: cancel measuring table display. Display next parameter.
Factory setting:
Next point
TANK DESCRIPTION (815)
Entry
Enter tank description. (max. 32 alphanumeric characters)
Factory setting:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Table 18: (GROUP SELECTION
) OPERATING MENU
SETTINGS
LINEARISATION
– on-site operation
Parameter name
Description