Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
74
Hauser
EMPTY PRESSURE (710)
Display
Displays the pressure value for the lower calibration point (container empty).
See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
0.0
FULL CALIB. (315)
Entry
Enter level value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter,
you are assigning a level value to the pressure present at the device.
See also FULL
PRESSURE.
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
FULL PRESSURE (711)
Display
Displays the pressure value for the upper calibration point (container full).
See also FULL CALIB.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
High sensor limit (
see PRESS. SENS HILIM, Page 119)
ADJUSTED DENSITY (810)
Display
Displays the density calculated from the upper and lower level point.
Prerequisite:
• CALIBRATION MODE = Wet, LIN. MEASURAND = Level
DENSITY UNIT (812)
Selection
Select density unit.
Prerequisite:
• LIN. MEASURAND = Level, CALIBRATION MODE = Dry
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Options:
• g/cm
3
• kg/dm
3
• kg/m
3
• US lb/in
3
• US lb/ft
3
Factory setting:
kg/dm
3
ADJUST DENSITY (316)
Entry
Enter density of fluid.
Prerequisite:
• LIN. MEASURAND = Level, CALIBRATION MODE = Dry
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1000.0
Table 11: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description