Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
86
Hauser
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST.
UNIT FACT. M.
Prerequisite:
• COMB. MEASURAND = Height and Mass, MASS UNIT = User unit
• COMB. MEASURAND = %-Height and Mass, MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT M parameter. The measured value is displayed with the additional
text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. M (703)
Entry
Enter conversion factor for a customer-specific mass unit.
The conversion factor must be entered in relation to the SI unit "kg".
See also
CUSTOMER UNIT M.
Prerequisite:
• COMB. MEASURAND = Height and Mass, MASS UNIT = User unit
• COMB. MEASURAND = %-Height and Mass, MASS UNIT = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 10 kg
i
1 bucket
– Entry CUSTOMER UNIT M: bucket
– Entry CUST. UNIT FACT. M: 0.1
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
LEVEL MIN (755)
Entry
Enter the minimum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum level to be expected, the more
accurate the measurement result.
!
Note!
• The following applies for the setting LEVEL MODE "Height Linearized" and ASSIGN
CURRENT "Linear":
If you enter a new value for LEVEL MIN, the value for SET LRV is also changed. Use
SET LRV to assign a height to the lower current value. If you want to assign the lower
current value a value other than that for LEVEL MIN, you must enter the desired value
for SET LRV. (
SET LRV, Page 98 and ASSIGN CURRENT, Page 113)
Factory setting:
0.0
LEVEL MAX (712)
Entry
Enter the maximum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the maximum level to be expected, the more
accurate the measurement result.
!
Note!
• The following applies for the setting LEVEL MODE "Height Linearized" and ASSIGN
CURRENT "Linear":
If you enter a new value for LEVEL MAX, the value for SET URV is also changed. Use
SET URV to assign a height to the upper current value. If you want to assign the upper
current value a value other than that for LEVEL MAX, you must enter the desired
value for SET URV. (
SET URV, Page 98 and ASSIGN CURRENT, Page 113)
Factory setting:
100.0
Table 13: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description