Appendix
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
142
Hauser
8.3
Confirming messages
Depending on the settings for the ALARM DISPL. TIME (
Page 129) and ACK. ALARM MODE
(
Page 128) parameters, the following measures should be taken to clear a message:
If the on-site display displays a message, you can delete it with the
F
-key.
If there are several messages, the on-site display shows the message which has the highest priority
(see also Section 8.1). Once you have deleted this message using the
F
-key, the message with the
next highest priority is displayed. You can use the
F
-key to delete each message, one after the other.
The ALARM STATUS parameter continues to display all the messages present.
9
Appendix
9.1
Operating menu for on-site display, Digital
communication
!
Note!
• The entire menu is depicted on the following pages.
• The menu has a different structure depending on the measuring mode selected. This means that
some function groups are only displayed for one measuring mode, e.g. "LINEARISATION"
function group for the Level measuring mode (Menu path: (GROUP SELECTION
)
OPERATING MENU
SETTINGS
BASIC SETUP).
• In addition, there are also parameters that are only displayed if other parameters are appropriately
configured. For example the Customer Unit P parameter is only displayed if the "User unit" option
was selected for the PRESS. ENG. UNIT parameter. These parameters are indicated with a "*".
• For a description of the parameters, please refer to chapter 7 "Description of parameters". The
exact dependency of individual parameters on one another is explained here.
Settings
1)
1)
Menu path for ALARM DISPL. TIME and ACK. ALARM MODE: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
MESSAGES
Measures
– ALARM DISPL. TIME = 0 s
– ACK. ALARM MODE = off
– Rectify cause of the message (see also Section 8.1).
– ALARM DISPL. TIME > 0 s
– ACK. ALARM MODE = off
– Rectify cause of the message (see also Section 8.1).
– Wait for the alarm display time to elapse.
– ALARM DISPL. TIME = 0 s
– ACK. ALARM MODE = on
– Rectify cause of the message (see also Section 8.1).
– Confirm message using ACK. ALARM parameter.
– ALARM DISPL. TIME > 0 s
– ACK. ALARM MODE = on
– Rectify cause of the message (see also Section 8.1).
– Confirm message using ACK. ALARM parameter.
– Wait for the alarm display time to elapse. If a message appears and the alarm
display time elapses before the message has been acknowledged, the message
will be cleared once it has been acknowledged.