Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
129
ACK. ALARM (500)
Selection
Acknowledge alarm.
Prerequisite:
• ACK. ALARM MODE = on
Options:
• Abort
• Confirm
The cause of the alarm must be eliminated, the message must be acknowledged via the
ACK. ALARM parameter and, where applicable, the ALARM DISPL. TIME (
Page 129)
has to have elapsed before the device starts measuring again following an alarm.
See also these Operating Instructions, Section 8.3 "Confirming messages".
Factory setting:
Abort
RESET ALL ALARMS (603)
Selection
Use this parameter to reset all the messages of the LAST DIAG. CODE parameter.
Options:
• Abort
• Confirm
Factory setting:
Abort
ERROR No.
Entry
For "Error"-type messages, you can decide whether the device should behave as in the
event of an alarm (A) or as in the event of a warning (W). Enter the corresponding
message number for this parameter.
See also SELECT ALARMTYPE.
See also these Operating Instructions, Section 8.1 "Messages" and Section 8.2
"Response of outputs to errors".
Prerequisite:
• Digital communication
SELECT ALARMTYPE
(595) – Entry
(600) – Selection
For "Error"-type messages, you can decide whether the device should behave as in the
event of an alarm (A) or as in the event of a warning (W).
See also ERROR No.
See also these Operating Instructions, Section 8.2 "Response of outputs to errors".
Options
:
• Alarm (A): output current assumes a defined value.
• Warning (W): device continues measuring
On-site operation:
1.
Enter the corresponding message number for ERROR No. field.
2.
Select "Alarm" or "Warning" option.
Digital communication:
1.
Enter the corresponding message number via the ERROR No. parameter.
2.
Use the SELECT ALARMTYPE parameter to select the "Alarm" or "Warning" option.
ALARM DELAY (336)
Entry
Enter alarm response time for all "Error" messages.
!
Note!
There is no alarm if the cause of the error is eliminated within the alarm delay time.
Input range:
0...100 s
Factory setting:
0.0 s
ALARM DISPL. TIME (480)
Entry
Enter alarm display time for all "Error" messages. Once the cause of the error is rectified,
the alarm display time starts running.
!
Note!
The following applies if the setting for ACK. ALARM MODE = on:
If an alarm appears and the alarm display time elapses before the alarm has been
acknowledged, the message will be cleared once it has been acknowledged.
See also these Operating Instructions, Section 8.3 "Confirming messages".
Input range:
0...999.9 s
Factory setting:
0.0 s
Table 33: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
MESSAGES
Parameter name
Description