Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
128
Hauser
SIM. LEVEL (714)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisite:
• MEASURING MODE = Level and SIMULATION MODE = Level
SIM. TANK CONT. (715)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisites:
• MEASURING MODE = Level, LEVEL MODE = Pressure Linearized and
SIMULATION MODE = Tank content
• MEASURING MODE = Level, LEVEL MODE = Height Linearized and
SIMULATION MODE = Tank content
SIM. CURRENT (270)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisite:
• SIMULATION MODE = Current value
Factory setting:
Current current value
SIM. ERROR NO. (476)
Entry
#
Warning!
The SIMULATION parameter overwrites fault states (alarm/warning) that are actually
present. When the simulation is ended, the fault states (alarm/warning) still persist but
are no longer displayed! When the device is restarted it returns to its fault state.
Enter message number.
See also SIMULATION MODE.
See also these Operating Instructions, Section 8.1 "Messages", "Code" table column.
Prerequisite:
• SIMULATION MODE = Alarm/Warning
Factory setting:
613 (simulation active)
Table 33: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
MESSAGES
Parameter name
Description
ALARM STATUS (046)
Display
Displays the current messages present.
See also these Operating Instructions,
Section 8.1. "Messages" and Section 8.3 "Confirming messages".
On-site display
• The measured value display shows the message with the highest priority.
• The ALARM STATUS parameter shows all the messages in descending order of
priority. You can scroll through all the messages present with the
O
or
S
key.
Operating program
• The "Status" field and the ALARM STATUS parameter show the message with the
highest priority.
LAST DIAG. CODE (564)
Display
Displays the last messages that occurred and were eliminated.
!
Note!
• On-site display: you can scroll through the last 15 messages with the
O
or
S
key.
• Digital communication: the last message appears on the display.
• Use the RESET ALL ALARMS parameter to delete the messages listed in the LAST
DIAG. CODE parameter.
ACK. ALARM MODE (401)
Selection
Switch on acknowledge alarm mode.
See also ACK. ALARM.
Options:
• On
• Off
Factory setting:
Off
Table 32: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
SIMULATION
Parameter name
Description