5.Description of Function Codes
EM15 User's Manual
62
b5-44
AI curve selection
Default
H321
Setting
Range
Unit’s digit:AI1 curve selection
1
curve 1(2 point, refer b5-07~b5-10)
2
curve 2(2 point, refer b5-12~b5-15)
3
curve 3(2 point, refer b5-17~b5-20)
4
curve 4(4 point, refer b5-22~b5-29)
5
curve 5(4 point, refer b5-30~b5-37)
Ten’s digit:AI2curve selection,same as above
Hundred’s digit:AI3 curve selection,same as above
b5-45
AI lower than minimum input setting selection
Default
H.000
Setting
Range
Unit’s digit:AI1 lower than minimum input setting
0
corresponding minimum input setting
1
0.0%
Ten’s digit:AI2 lower than minimum input setting selection, same as above
Hundred’s digit:AI3 lower than minimum input setting selection, same as above
The AI terminals (AI1 to AI3) of EM15 all support the corresponding setting jump function, which fixes the AI input
corresponding setting at the jump point when AI input corresponding setting jumps around the jump range.
For example:
AI1 input voltage fluctuation around 5.00V and the amplitude range is 4.90V~5.10V. AI1 minimum input 0.00V
corresponds to 0.00% and maximum input 10.00V corresponds to 100.0%. The detected AI1 input corresponding
setting varies between 49.0% and 51.0%.
If you set jump point b5-38 to 50.0% and jump amplitude b5-39 to 1.0%, then frequency inverter obtained AI1 input
corresponding setting is fixed to 50.0%, eliminating the fluctuation effect.
5.7 Group b6: Pulse/analog output terminals
b6-00
FMP function selection
Default
0
b6-01
AO1 output function selection
Default
0
b6-02
AO2 output function selection
Default
1
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP output frequency" (b6-03).
The value of b6-03 is between 0.01 kHz and 50.00 kHz.
The output range of AO1 is 0V~10 V or 0mA~20mA. The output range of AO2 is 0~10V, The relationship between
pulse and analog output ranges and corresponding functions is listed in the following table.
Value
Function
Range (Corresponding to Pulse or Analog Output Range 0.0%~100.0%)
0
Running frequency
0Hz~ maximum output frequency
1
Setting frequency
0Hz~ maximum output frequency
2
Output current
0 ~2 times of rated motor current
3
Output torque (absolute
value)
0~ 2 times of rated motor torque(absolute value of torque)
4
Output power
0 ~2 times of rated power
5
Output voltage
0 ~1.2 times of rated frequency inverter DC bus voltage
6
Pulse input
0.01 kHz ~100.00 kHz
7
AI1
0V~10 V
8
AI2
0V~10 V
9
AI3
0V~10 V
12
Communication setting
0~32767
13
Motor rotational speed
0~rotational speed corresponding to maximum output frequency
14
Output current
0.0A~1000.0 A
15
Output voltage
0.0V~1000.0 V