5.Description of Function Codes
EM15 User's Manual
96
frequency is exceeded, as shown in the following figure.
Diagram 5-30 Manual torque boost
d2-03
Multi-point V/F frequency 1 (F1)
Default
0.00 Hz
Setting Range
0.00 Hz ~ d2-05
d2-04
Multi-point V/F voltage 1 (V1)
Default
0.0%
Setting Range
0.0%~100.0%
d2-05
Multi-point V/F frequency 2 (F2)
Default
0.00 Hz
Setting Range
d2-03 to d2-07
d2-06
Multi-point V/F voltage 2 (V2)
Default
0.0%
Setting Range
0.0%~100.0%
d2-07
Multi-point V/F frequency 3 (F3)
Default
0.00 Hz
Setting Range
d2-05 ~ maximum frequency
d2-08
Multi-point V/F voltage 3 (V3)
Default
0.0%
Setting Range
0.0%~100.0%
When d2-00 set to 1, these six parameters are used to define the multi-point V/F curve.
The multi-point V/F curve is set based on the motor's load characteristic. The relationship between voltages and
frequencies is: V1 < V2 < V3, F1 < F2 < F3. Diagram 6-32 shows the setting of multi-point V/F curve.
At low frequency, higher voltage may cause motor overheat or even burnt and cause frequency inverter over
current stall or over current protection.