Appendix II
EM15 User’s Manual
140
Code
Parameter Name
Functional description
Default
Property
bA-01 Baud ratio setting
Unit's digit: Modbus baud ratio.
0: 300 BPS
1: 600 BPS
2: 1200 BPS
3: 2400 BPS
4: 4800 BPS
5: 9600 BPS
6: 19200 BPS
7: 38400 BPS
5
☆
bA-02 Modbus Data format
0: No check, data format <8,N,2>
1: Even parity check, data format<8,E,1>
2: Odd Parity check, data format<8,O,1>
3: No check, data format <8,N,1>
Valid for Modbus
0
☆
bA-03 Broadcast address
0~247 (0: Broadcast address)
Valid for Modbus
1
☆
bA-04 Modbus response delay
0~20 ms
Only valid for Modbus
2 ms
☆
bA-05 Communication timeout
0.0s:invalid
0.1s~60.0s
Valid for Modbus
0.0s
☆
bA-06
Modbus protocol data
transmission format
selection
Unit's digit: Modbus protocol.
0: Non-standard Modbus protocol
1: Standard Modbus protocol
Ten's digit: Profibus-DP
0:PP01
1:PP02
2:PP03
3:PP05
31
☆
bA-07
Communication reading
current resolution
0: 0.01A
1: 0.1A
0
☆
Group bb: Fault and Protection Setting
bb-00 G/P type selection
0: P type
1: G type
1
☆
bb-01
Motor overload protection
selection
0: Disabled
1: Enabled
1
☆
bb-02
Motor overload protection
gain
0.20~10.00
1.00
☆
bb-03
Motor overload
pre-warning coefficient
50%~100%
80%
☆
bb-09 Fault auto reset times
0~20(Unlimited number of times)
0
☆
bb-10
Relay action selection
during fault auto reset
0: Not act
1: Act
0
☆
bb-11
Time interval of fault auto
reset
0.1s~100.0s
1.0s
☆
bb-12
Input phase loss
protection/contactor
energizing protection
Unit's digit: Input phase loss protection
0: Disabled
1: Enabled
11
☆