EM15 User’s Manual
Appendix I
123
100F
Load speed
101F
Main frequency X display
1020
Auxiliary frequency Y display
Note:
Communication setting value is the percentage of relative value, 10000 corresponds to 100%, -10000
correspond to -100.00%.
Control command input frequency inverter: (write in only)
Command word address
Command function
2000
0001: Forward running
0002: Reverse running
0003: Forward jog
0004: Reverse jog
0005: Free stop
0006:Decelarating stop
0007: Fault reset
Read inverter status: (read only)
Command word address
Command function
3000
0001: Forward running
0002: Reverse running
0003: Stop
Parameter locking password collation: (If the feedback is the 8888H, it indicates the password collation passed)
Password address
Contents of input password
1F00
*****
Digital output terminal control: (write in only)
Address Of locking password command
Contents of locking password command
2001
BIT0: DO1 output control
BIT1: DO2 output control
BIT2: Relay 1 output control
BIT3: Relay 2 output control
BIT4: FMR output control
BIT5: VDO1
BIT6: VDO2
BIT7: VDO3
BIT8: VDO4
BIT9: VDO5
Analog output AO1 control: (write in only)
Command word address
Command function
2002
0~7FFF indicates 0%~100%
Analog output AO2 control: (write in only)
Command word address
Command function
2003
0~7FFF indicates 0%~100%