5.Description of Function Codes
EM15 User's Manual
44
jump frequencies are valid during acceleration/deceleration.
Diagram 5-7 Diagrams when the jump frequencies are valid during acceleration/deceleration
b2-13
Frequency switchover point between acceleration time 1 and
acceleration time 2
Default
0.00Hz
Setting Range
0.00 Hz ~maximum frequency
b2-14
Frequency switchover point between deceleration time 1 and
deceleration time 2
Default
0.00Hz
Setting Range
0.00 Hz ~maximum frequency
This function is valid when motor 1 is selected and acceleration/deceleration time switchover is not performed by
means of DI terminal. It is used to select different groups of acceleration/ deceleration time based on the running
frequency range rather than DI terminal during the running process of the frequency inverter.
Diagram 5-8 Acceleration/deceleration time switchover
During acceleration, if the running frequency is smaller than the value of b2-13, acceleration time 1 is selected. If the
running frequency is larger than the value of b2-13, acceleration time 2 is selected.
During deceleration, if the running frequency is larger than the value of b2-14, deceleration time 1 is selected. If the
running frequency is smaller than the value of b2-14, deceleration time 2 is selected.
b2-15
Reverse running
Default
0
Setting
Range
0
Enabled
1
Disabled
It is used to set whether the frequency inverter allows reverse rotation. In the applications where reverse rotation is