Figure 7-30: Identifying the Hold Off Distance/UNZ in the Echo Curve Plot
A. Amplitude, mV
B. Distance, m
C. Hold Off Distance/UNZ
D. Disturbance
E. Surface peak
F. Surface Threshold
2. Set the Hold Off Distance/UNZ to the desired value.
a) Select
Setup
→
Tank
.
a) Select the
Probe
tab.
b) In the
Hold Off Distance/UNZ
box, type the desired value.
c) Select
Store
.
Set the hold off distance/upper null zone using a handheld
communicator
Prerequisites
Note
By adjusting the Hold Off Distance/UNZ, the measuring range is reduced.
Note
Before changing the Hold Off Distance/UNZ, check entered value for the high alarm limit.
The high alarm limit must be outside the Hold Off Distance/UNZ.
Procedure
1. Use the Echo Curve plot to verify if there are disturbances in the upper part of the
tank.
Reference Manual
Service and troubleshooting
00809-0100-4530
April 2019
Reference Manual
229
Содержание Rosemount 5300 Series
Страница 1: ...Reference Manual 00809 0100 4530 Rev FA April 2019 Rosemount 5300 Level Transmitter Guided Wave Radar ...
Страница 26: ...Transmitter overview Reference Manual April 2019 00809 0100 4530 26 Rosemount 5300 Level Transmitter ...
Страница 112: ...Electrical installation Reference Manual April 2019 00809 0100 4530 112 Rosemount 5300 Level Transmitter ...
Страница 158: ...Configuration Reference Manual April 2019 00809 0100 4530 158 Rosemount 5300 Level Transmitter ...
Страница 168: ...Operation Reference Manual April 2019 00809 0100 4530 168 Rosemount 5300 Level Transmitter ...
Страница 244: ...Service and troubleshooting Reference Manual April 2019 00809 0100 4530 244 Rosemount 5300 Level Transmitter ...
Страница 380: ...Product certifications Reference Manual April 2019 00809 0100 4530 380 Rosemount 5300 Level Transmitter ...
Страница 396: ...Configuration parameters Reference Manual April 2019 00809 0100 4530 396 Rosemount 5300 Level Transmitter ...
Страница 487: ...Reference Manual 00809 0100 4530 April 2019 Reference Manual 487 ...