will also need the National Instruments Communication Manager software (see
the RRM software for FOUNDATION Fieldbus
5.3
Host system integration
5.3.1
Confirm system readiness (HART
®
only)
Confirm HART
®
revision capability
If using HART based control or asset management systems, confirm the HART capability of
those systems prior to transmitter installation. Not all systems are capable of
communicating with HART Revision 7 protocol.
Transmitters with a firmware version 2F0 or later can be configured for either HART
Revision 5 or 7.
Confirm correct device driver
Procedure
•
Verify that the latest Device Driver (DD/DTM
™
) is loaded on your systems to ensure
.
•
Download the latest Device Driver from
Table 5-1: Rosemount 5300 Device Revisions and Files
Find Device Driver
HART
®
Universal Revision
2F0 or later
7
4
5
3
2A2 - 2E0
5
3
(1)
Firmware version is printed on the transmitter head label, e.g. SW 2E0 or can be found in
Rosemount Radar Master (select
Device
→
Properties
).
(2)
Device revision is printed on the transmitter head label, e.g. HART Dev Rev 4.
Switch HART
®
revision mode
If the HART configuration tool is not capable of communicating with HART Revision 7, the
device will load a generic menu with limited capability. To switch the HART revision mode
from the generic menu:
Procedure
1. Locate the “Message” field.
2. In the Message field, enter
HART5
or
HART7
and then 27 trailing spaces.
Reference Manual
Configuration
00809-0100-4530
April 2019
Reference Manual
115
Содержание Rosemount 5300 Series
Страница 1: ...Reference Manual 00809 0100 4530 Rev FA April 2019 Rosemount 5300 Level Transmitter Guided Wave Radar ...
Страница 26: ...Transmitter overview Reference Manual April 2019 00809 0100 4530 26 Rosemount 5300 Level Transmitter ...
Страница 112: ...Electrical installation Reference Manual April 2019 00809 0100 4530 112 Rosemount 5300 Level Transmitter ...
Страница 158: ...Configuration Reference Manual April 2019 00809 0100 4530 158 Rosemount 5300 Level Transmitter ...
Страница 168: ...Operation Reference Manual April 2019 00809 0100 4530 168 Rosemount 5300 Level Transmitter ...
Страница 244: ...Service and troubleshooting Reference Manual April 2019 00809 0100 4530 244 Rosemount 5300 Level Transmitter ...
Страница 380: ...Product certifications Reference Manual April 2019 00809 0100 4530 380 Rosemount 5300 Level Transmitter ...
Страница 396: ...Configuration parameters Reference Manual April 2019 00809 0100 4530 396 Rosemount 5300 Level Transmitter ...
Страница 487: ...Reference Manual 00809 0100 4530 April 2019 Reference Manual 487 ...