K.5.3
ABB TotalFlow
Figure K-4: Wiring Diagram for Connecting Rosemount 5300 Modbus to ABB
TotalFlow
COMM 1/2
1 VBAT
2 GND
3
4
5
6 Bus -
7
8 Bus +
9
POWER +
POWER -
MA
MB
$
%
A. Rosemount 5300 Modbus
B. TOTALFLOW
Table K-8: Parameter Values (In Case of ABB TotalFlow)
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 5300 Level Transmitter. In this case, register 1302 needs to have 1303 entered
as the address etc.
Reference Manual
Rosemount 5300 with HART
®
to Modbus
®
Converter
00809-0100-4530
April 2019
Reference Manual
483
Содержание Rosemount 5300 Series
Страница 1: ...Reference Manual 00809 0100 4530 Rev FA April 2019 Rosemount 5300 Level Transmitter Guided Wave Radar ...
Страница 26: ...Transmitter overview Reference Manual April 2019 00809 0100 4530 26 Rosemount 5300 Level Transmitter ...
Страница 112: ...Electrical installation Reference Manual April 2019 00809 0100 4530 112 Rosemount 5300 Level Transmitter ...
Страница 158: ...Configuration Reference Manual April 2019 00809 0100 4530 158 Rosemount 5300 Level Transmitter ...
Страница 168: ...Operation Reference Manual April 2019 00809 0100 4530 168 Rosemount 5300 Level Transmitter ...
Страница 244: ...Service and troubleshooting Reference Manual April 2019 00809 0100 4530 244 Rosemount 5300 Level Transmitter ...
Страница 380: ...Product certifications Reference Manual April 2019 00809 0100 4530 380 Rosemount 5300 Level Transmitter ...
Страница 396: ...Configuration parameters Reference Manual April 2019 00809 0100 4530 396 Rosemount 5300 Level Transmitter ...
Страница 487: ...Reference Manual 00809 0100 4530 April 2019 Reference Manual 487 ...