On wall:
4X
2. Mount the transmitter with probe to the bracket.
3X
3.5.5
Tank connection with Tri-Clamp
®
Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Procedure
1. Place a suitable gasket on top of the tank flange.
2. Lower the transmitter and probe into the tank.
3. Tighten the clamp to the recommended torque (see the manufacturer’s instruction
manual).
Mechanical installation
Reference Manual
April 2019
00809-0100-4530
74
Rosemount 5300 Level Transmitter