Figure 8-1: Device Properties Window
A. Serial No
B. Software/Firmware
C. Safety Device (QS option)
8.5
Installation in SIS applications
The device should be installed and configured as a level sensing device per manufacturer’s
instructions. The materials must be compatible with process conditions and process fluids.
No special installation is required in addition to the standard installation practices outlined
in this manual.
Environmental and operational limits are available in
Appendix A: Specifications and
The loop must be designed so that the terminal voltage does not drop below the
minimum input voltage when the transmitter output is 22.5 mA. See values in
.
Table 8-3: Minimum Input Terminal Voltage (U
i
) at Different Currents
Hazardous
approval
Current
3.60 mA
3.75 mA
21.75 mA
22.50 mA
Minimum input voltage (U
i
)
Non-Hazardous /
Intrinsically Safe /
Non-sparking
Installations
16 Vdc
16 Vdc
11 Vdc
11 Vdc
Explosion-proof /
Flameproof
Installations
20 Vdc
20 Vdc
15.5 Vdc
15.5 Vdc
Safety Instrumented Systems (4-20 mA only)
Reference Manual
April 2019
00809-0100-4530
248
Rosemount 5300 Level Transmitter
Содержание Rosemount 5300 Series
Страница 1: ...Reference Manual 00809 0100 4530 Rev FA April 2019 Rosemount 5300 Level Transmitter Guided Wave Radar ...
Страница 26: ...Transmitter overview Reference Manual April 2019 00809 0100 4530 26 Rosemount 5300 Level Transmitter ...
Страница 112: ...Electrical installation Reference Manual April 2019 00809 0100 4530 112 Rosemount 5300 Level Transmitter ...
Страница 158: ...Configuration Reference Manual April 2019 00809 0100 4530 158 Rosemount 5300 Level Transmitter ...
Страница 168: ...Operation Reference Manual April 2019 00809 0100 4530 168 Rosemount 5300 Level Transmitter ...
Страница 244: ...Service and troubleshooting Reference Manual April 2019 00809 0100 4530 244 Rosemount 5300 Level Transmitter ...
Страница 380: ...Product certifications Reference Manual April 2019 00809 0100 4530 380 Rosemount 5300 Level Transmitter ...
Страница 396: ...Configuration parameters Reference Manual April 2019 00809 0100 4530 396 Rosemount 5300 Level Transmitter ...
Страница 487: ...Reference Manual 00809 0100 4530 April 2019 Reference Manual 487 ...