Mechanical Installation
72
5.10.4
Mains supply connection (X3, X4)
Drives in the PSD series can be supplied as follows:
•
IC830DPzzz06: 1 or 3 phase industrial supply networks (not more than 200 kA
symmetrical rated current at 120 V and 240 V).
•
IC830DPzzz07: 3 phase industrial supply networks (not more than 200 kA symmetrical
rated current at 240 V, 400 V and 480 V).
•
Connection to other voltage types of supply networks is possible with an additional
isolating transformer (
# 102). Periodic overvoltages between phases (L1, L2, L3)
and the housing of the drive must not exceed 1000 V peak. In accordance with IEC
61800, voltage spikes (< 50 µs) between phases must not exceed 1000 V. Voltage
spikes (< 50 µs) between a phase and the housing must not exceed 2000 V.
IC830DP00306 to IC830DP00606 (X3)
Pin
Signal
Description
4
L1
Line 1
5
L2
Line 2
6
L3
Line 3
7
PE
Protective Earth
IC830DP01206 (X3)
5
L1
Line 1
6
L2
Line 2
7
L3
Line 3
8
PE
Protective Earth
IC830DP02406 & IC830DP00307 to IC830DP02407 (X4)
Pin
Signal
Description
1
L1
Line 1
2
L2
Line 2
3
L3
Line 3
4
PE
Protective Earth