PACMotion™ PSD Installation and User Manual
Section 5
GFK-3168A
September 2020
Setup
93
5.18.4.5
Recovering Communications with a Drive on an Un-Reachable IP
Address
If IP.MODE has been set to 1 (using software defined static IP), the drive will boot up on an IP
Address that may be unreachable with the
host computer’s
settings.
If the IP address prevents communication, the IP settings can be reset to default by the following
procedure:
Set both rotary switches to 0
Hold down button B1 (top-side of drive) for 5 seconds.
The display will flash 0.0.0.0 and then attempt to discover an address by DHCP.
Without removing logic power from the drive, use PACMotion Workbench to connect to the drive,
reconfigure the IP address settings as desired, and store the values to non-volatile memory.
5.19
EtherCat Interface (X5/X6/EtherCat)
The motion bus interface has RJ-45 connectors and can be used for communicating with various
fieldbus devices depending on the used drive version.
PSD X5/X6
PSD X6
Note: Do not connect the Ethernet line for the PC or PAC with the set up software to the motion
bus interface X5/X6.
The set up Ethernet cable must be connected to X11.
Color
Name
Indication
Green
Link
On = receive signal valid
Yellow
Activity
Blink = Transmit or Receive packet