PACMotion™ PSD Installation and User Manual
Section 5
GFK-3168A
September 2020
Mechanical Installation
67
5.9.3
Shielding connection to the drive
You can connect cable shielding directly to the drive by using grounding plates, shield connection
clamps, and a motor connector with strain relief and grounding plate.
5.9.3.1
Grounding plates
Mount the grounding plates to the drive as shown in the photos below.
5.9.3.2
IC830DP0306 to P1206 types:
L-shape grounding plate (EU only)
Figure 28: IC830DP02406 & xzzz07 types: flat grounding plate
5.9.3.3
Shield connection clamps
Use shield connection clamps (see accessories manual). These hook into the grounding plate and
ensure optimum contact between the shield and the grounding plate.
Emerson recommends using Phoenix Contact SK14 shield clamps with clamp range of 6-13mm.
Figure 29: Shield Connection Lamps