PACMotion™ PSD Installation and User Manual
Section 4
GFK-3168A
September 2020
Technical Description and Data
15
Electrical Data
Units
IC830D
P00306
IC830D
P00606
IC830D
P01206
IC830D
P02406
at 240 V
Arms 3
6
12
24
Peak output current
(for 5 s, ± 3%)
Arms 9
18
30
48
Continuous output power @ rated input current
at 1x120 V
VA
312.5
625
1250
-
at 1x240 V
VA
625
1250
2500
-
at 3x120 V
VA
312.5
625
1250
-
at 3x240 V
VA
625
1250
2500
5000
Peak output power (for 1 s)
at 1x120 V
kVA
0.937
1.875
3.125
-
at 1x240 V
kVA
1.875
3.750
6.250
-
at 3x120 V
kVA
0.937
1.875
3.125
-
at 3x240 V
kVA
1.875
3.750
6.250
10
Technical data for
regen circuit
—
Motor inductance min.
at 120 V
mH
1.3
0.6
0.5
0.3
at 240 V
mH
2.5
1.3
1
0.6
Motor inductance
max.
mH
250
125
100
60
Thermal dissipation,
output stage disable
W
max. 20
max. 20
max. 20
max. 25
Thermal dissipation
at rated current
W
31
57
137
175
Noise emission (low
speed/high speed
fan)
dB(A) N/A
33/39
37/43
41/56
Aux. voltage supply
(PELV)
V
24 V (±10%, check voltage drop)
-current B, P, T
types without/with
motor brake
A
0.5 / 1.7
0.6 / 1.8
0.7 / 1.9
1.0 / 2.5
-current M type
without/with motor
brake
A
0.8 / 2.0
0.9 / 2.1
1.0 / 2.2
1.3 / 2.8
4.6
Electrical Data IC830DPzzz07
Electrical data
Units
IC830D
P00307
IC830D
P00607
IC830D
P01207
IC830D
P02407
Rated supply voltage
(L1/L2/L3)
V
3 x 240 V to 480 V ±10%
Rated supply input
frequency
Hz
AC with 50 Hz to 400 Hz ±5% or DC
Rated input power for S1
operation
kVA
2.24
4.49
7.65
15.2
Rated input current @ 40°C surrounding air temperature
at 3x240 V
A
2.7
5.4
9.2
18.3
at 3x400 V
A
2.7
5.4
9.2
18.3
at 3x480 V
A
2.7
5.4
9.2
18.3