4.3.1
Configure Volume Flow Type for gas applications
Display
Not available
ProLink II
ProLink
>
Configuration
>
Flow
>
Vol Flow Type
ProLink III
Device Tools
>
Configuration
>
Process Measurement
>
Flow
Field Communicator
Configure
>
Manual Setup
>
Measurements
>
GSV
>
Volume Flow Type
>
Standard Gas Volume
Overview
Volume Flow Type
controls whether liquid or gas standard volume flow measurement is
used.
Restriction
If you are using the petroleum measurement application, you must set
Volume Flow Type
to
Liquid
. Gas
standard volume measurement is incompatible with the petroleum measurement application.
Restriction
If you are using the concentration measurement application, you must set
Volume Flow Type
to
Liquid
.
Gas standard volume measurement is incompatible with the concentration measurement
application.
Procedure
Set
Volume Flow Type
to
Gas Standard Volume
.
4.3.2
Configure Standard Gas Density
Display
Not available
ProLink II
ProLink
>
Configuration
>
Flow
>
Std Gas Density
ProLink III
Device Tools
>
Configuration
>
Process Measurement
>
Flow
Field Communicator
Configure
>
Manual Setup
>
Measurements
>
GSV
>
Gas Ref Density
Overview
The
Standard Gas Density
value is used to convert the measured flow data to the standard
reference values.
Prerequisites
Ensure that
Density Measurement Unit
is set to the measurement unit you want to use for
Standard Gas Density
.
Configure process measurement
Configuration and Use Manual
35
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......