
2.
Ensure
Loop Current Mode
(
mA Output Action
) is configured appropriately.
Options
Description
Enabled
The primary mA output reports process data as configured.
Disabled
The primary mA output is fixed at 4 mA and does not report process
data.
Important
If you use ProLink II or ProLink III to set
HART Address
to
0
, the program automatically enables
Loop Current Mode
. If you use ProLink II or ProLink III to set
HART Address
to any other value, the
program automatically disables
Loop Current Mode
. This is designed to make it easier to
configure the transmitter for legacy behavior. Always verify
Loop Current Mode
after setting
HART Address
.
3.
(Optional) Enable and configure
Burst Parameters
.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on
the network requires burst mode communication.
4.
(Optional) Configure
HART Variables
.
Configure burst parameters
Display
Not available
ProLink II
ProLink
>
Configuration
>
Device
>
Burst Setup
ProLink III
Device Tools
>
Configuration
>
Communications
>
Communications (HART)
Field Communicator
Configure
>
Manual Setup
>
Inputs/Outputs
>
Communications
>
Set Up Burst Mode
Overview
Burst mode is a mode of communication during which the transmitter regularly
broadcasts HART digital information over the mA output. The burst parameters control
the information that is broadcast when burst mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on the
network requires burst mode communication.
Procedure
1.
Enable
Burst Mode
.
2.
Set
Burst Mode Output
as desired.
Integrate the meter with the control system
Configuration and Use Manual
125
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......