For the relevant status alarms, change the setting of
Alarm Severity
to
Ignore
.
3.
If there are no active fault conditions, continue troubleshooting.
12.20
Check Frequency Output Maximum Pulse
Width
If
Frequency Output Maximum Pulse Width
is set incorrectly, the frequency output may report an
incorrect value.
Verify the configuration of
Frequency Output Maximum Pulse Width
.
For most applications, the default value for
Frequency Output Maximum Pulse Width
is
appropriate. This corresponds to a 50% duty cycle.
12.21
Check Frequency Output Scaling Method
If
Frequency Output Scaling Method
is set incorrectly, the frequency output may report an
incorrect value.
1.
Verify the configuration of
Frequency Output Scaling Method
.
2.
If you changed the setting of
Frequency Output Scaling Method
, check the settings of all
other frequency output parameters.
12.22
Check Frequency Output Fault Action
The
Frequency Output Fault Action
controls the behavior of the frequency output if the
transmitter encounters an internal fault condition. If the frequency output is reporting a
constant value, the transmitter may be in a fault condition.
1.
Check the status alarms for active fault conditons.
2.
If there are active fault conditions, the transmitter is performing correctly. If you
want to change its behavior, consider the following options:
•
Change the setting of
Frequency Output Fault Action
.
•
For the relevant status alarms, change the setting of
Alarm Severity
to
Ignore
.
3.
If there are no active fault conditions, continue troubleshooting.
12.23
Check Flow Direction
If
Flow Direction
is set inappropriately for your process, the transmitter may report
unexpected flow values or totals.
Troubleshooting
Configuration and Use Manual
237
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......