Procedure
Set
Discrete Output Fault Action
as desired.
The default setting is
None
.
Options for Discrete Output Fault Action
Options for Discrete Output Fault Action
Table 6-11:
Label
Discrete output behavior
Polarity=
Active High
Polarity=
Active Low
Upscale
•
Fault: discrete output is ON
(site-specific voltage)
•
No fault: discrete output is con-
trolled by its assignment
•
Fault: discrete output is OFF
(0 V)
•
No fault: discrete output is con-
trolled by its assignment
Downscale
•
Fault: discrete output is OFF
(0 V)
•
No fault: discrete output is con-
trolled by its assignment
•
Fault: discrete output is ON
(site-specific voltage)
•
No fault: discrete output is con-
trolled by its assignment
None
(default)
Discrete output is controlled by its assignment
Fault indication with the discrete output
To indicate faults via the discrete output, set parameters as follows:
•
Discrete Output Source
=
Fault
•
Discrete Output Fault Action
=
None
Note
If
Discrete Output Source
is set to
Fault
and a fault occurs, the discrete output is always ON. The setting
of
Discrete Output Fault Action
is ignored.
6.5
Configure events
An event occurs when the real-time value of a user-specified process variable moves past a
user-defined setpoint. Events are used to provide notification of process changes or to
perform specific transmitter actions if a process change occurs.
Your transmitter supports two event models:
•
Basic event model
•
Enhanced event model
Integrate the meter with the control system
120
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......