b. Read the frequency signal at the receiving device and compare it to the
transmitter output.
c. Choose
End
.
3.
Test the discrete output(s).
a. Press
Service Tools
>
Simulate
>
Simulate Outputs
>
Discrete Output Test
.
b. Choose
Off
.
c. Verify the signal at the receiving device.
d. Press
OK
.
e. Choose
On
.
f. Verify the signal at the receiving device.
g. Press
OK
.
h. Choose
End
.
Postrequisites
•
If the mA output reading was slightly off at the receiving device, you can correct this
discrepancy by trimming the output.
•
If the mA output reading was significantly off (±200 microamps), or if at any step the
reading was faulty, verify the wiring between the transmitter and the remote device,
and try again.
•
If the discrete output reading is reversed, check the setting of
Discrete Output Polarity
.
12.13
Check for radio frequency interference (RFI)
The transmitter's frequency output or discrete output can be affected by radio frequency
interference (RFI). Possible sources of RFI include a source of radio emissions, or a large
transformer, pump, or motor that can generate a strong electromagnetic field. Several
methods to reduce RFI are available. Use one or more of the following suggestions, as
appropriate to your installation.
Procedure
•
Eliminate the RFI source.
•
Move the transmitter.
•
Use shielded cable for the frequency output or discrete output.
-
Terminate the shielding at the output device. If this is impossible, terminate the
shielding at the cable gland or conduit fitting.
-
Do not terminate the shielding inside the wiring compartment.
-
360-degree termination of shielding is unnecessary.
Troubleshooting
234
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......