Diagnostics Optimization CT MODBUS RTU Technical Data
E300 Design Guide
213
Issue Number: 1
When
Motor Contactor Monitoring Enable
(
B29
) = On (1), then this parameter is used to monitor the state of the motor contactors. One of the elevator
drive inputs or I/O option inputs must be routed to this parameter, where the signal to activate the input comes from the motor contactors auxiliary
contacts.
When set to Off (0), the motor contactors are open, when set to On (1) the motor contactors are closed.
This input is used to generate
Trip 70 (
Mot con open
)
/
Trip 71 (
Mot con closd
)
.
If the motor contactors are to be connected to the elevator drive, route this parameter to a drive digital output, which will control the motor contactors.
When set to Off (0), the motor contactors will be opened.
When set to On (1), the motor contactors will be closed.
A volatile source parameter must be used to prevent the user from saving to On (1).
This indicates the measured contactor opening time delay in ms.
This is the time from when the brake apply delay starts to when the enable is removed –
Brake Control Apply Delay
(
D05
) –
Motor Torque Ramp Time
(
D02
). See the following diagram:
A negative time indicates that the contactor opened while current was flowing i.e. drive is disabled (via the motor contactors auxiliary contacts) during
the
Brake Control Apply Delay
(
D05
) or the
Motor Torque Ramp Time
(
D02
). Negative values can only occur in situations where the Motor contactor
B30
Motor Contactor Monitoring Input
Mode
Open-loop: RFC-A, RFC-S
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4 ms
Display Format
Standard
Decimal Places
0
Coding
RW
B31
Motor Contactor Control Output
Mode
Open-loop: RFC-A, RFC-S
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
4 ms
Display Format
Standard
Decimal Places
0
Coding
RW
B32
Motor Contactor Measured Delay Time
Mode
Open-loop: RFC-A, RFC-S
Minimum
0
Maximum
32767
Default
0
Units
ms
Type
16 Bit Volatile
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RO
Time
Sp
e
e
d
Profile completed here &
Motor contactor timing begins &
Brake contactor control output = 0
D05
D02
Drive disabled &
Motor contactor timing ends
B32