Diagnostics Optimization CT MODBUS RTU Technical Data
364
E300 Design Guide
Issue Number: 1
See
Date
(
J80
).
Date And Time Offset
(
J83
) is an offset, specified in hours, that can be applied to the
Time
(
J81
). If the offset applied causes the time to roll-over
midnight then the
Date
(
J80
) and
Day Of Week
(
J82
) are also modified. The offset is only applied when the clock source is a clock derived from a
keypad or option module, i.e.
Date/Time Selector
(
H32
) > 3. The offset can be used for time zone offsets or daylight saving time etc. It should be
noted that when the date and time is derived from an option module this may be in the form of UTC (Co-ordinated Universal Time) with an additional
offset also provided by the option module. The data and time is derived by adding the additional offset and the time from the option module and then
adding
Date And Time Offset
(
J83
).
See
Reset Energy Meter
(
H37
).
See
Reset Energy Meter
(
H37
).
J82
Day Of Week
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
6
Default
Units
Type
8 Bit Volatile
Update Rate
Background write
Display Format
Date
Decimal Places
0
Coding
RO, TE, ND, NC, PT
Value
Text
0
Sunday
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
J83
Date And Time Offset
Mode
Open-Loop, RFC-A, RFC-S
Minimum
-24.00
Maximum
24.00
Default
0.00
Units
Hours
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
J84
Energy Meter: MWh
Mode
Open-Loop, RFC-A, RFC-S
Minimum
-999.9
Maximum
999.9
Default
Units
MWh
Type
16 Bit Power Down Save
Update Rate
Background write
Display Format
Standard
Decimal Places
1
Coding
RO, ND, NC, PT
J85
Energy Meter: kWh
Mode
Open-Loop, RFC-A, RFC-S
Minimum
-99.99
Maximum
99.99
Default
Units
kWh
Type
16 Bit Power Down Save
Update Rate
Background write
Display Format
Standard
Decimal Places
2
Coding
RO, ND, NC, PT