Diagnostics Optimization CT MODBUS RTU Technical Data
284
E300 Design Guide
Issue Number: 1
T9 Analog Output 2 Source
(
F66
) defines the source parameter for analog output 2. The value of the source parameter is scaled with
Analog Output
2 Scaling
(
F67
) and if the scaling is greater than 1.000 the value is clamped between -100 % and +100 % or between 0 % and 100 % depending on
whether the output is bipolar or unipolar. The resulting value is then used to control the output.
The outputs provided with different hardware are given in the table below.
The output mode is defined by
Analog Output 2 Mode
(
AU24
) as shown in the table below.
See
T9 Analog Output 2 Source
(
F66
).
Many elevator controllers use relay derived outputs which have contact bounce. This contact bounce can generate spurious speed selection on start,
particularly for binary selection type inputs. This filter time in ms allows the user to apply a digital speed selection / deselection filter time such that any
intermediate speed selections caused by contactor bounce or by the processing of the elevator controller outputs will be filtered out from the elevator
drive control.
When set >0 this filter is applied when selecting and deselecting V1 to V10. This operation is used for binary selection.
When set <0 this filter is applied only when selecting V1 to V10. This mode may be used for priority based selection only.
F66
T9 Analog Output 2 Source
Mode
Open-Loop, RFC-A, RFC-S
Minimum
A00
Maximum
AB99
Default
A00
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Menu Param Alpha Numeric
Decimal Places
3
Coding
RW, PT, BU
Internal IO Identifier
(J66)
Analog Output 1
Analog Output 2
0: Standard Analog and Digital I/O
Bipolar Voltage
Bipolar Voltage
T9 Analog Output 2 Mode
(AU24)
Standard Analog and Digital I/O
Volt
-10 V to + 10 V
0-20 mA
Not possible
20-0 mA
Not possible
4-20 mA
Not possible
20-4 mA
Not possible
F67
Analog Output 2 Scaling
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0.000
Maximum
10.000
Default
1.000
Units
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
3
Coding
RW
F68
Start Speed Selection Filter
Mode
Open-Loop, RFC-A, RFC-S
Minimum
-200
Maximum
200
Default
20
Units
ms
Type
16 Bit User Save
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RW
F69
Encoder Thermistor Type
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE