Analog input 3
Default function
Motor thermistor input
Type of input
Bipolar single-ended analog voltage, or thermistor input
Mode controlled by...
Parameter
F52
Operating in Voltage mode (default)
Voltage range
± 10 V ± 2 %
Absolute maximum voltage range
± 36 V relative to 0 V
Operating in thermistor input mode
Supported thermistor types
Din 4408, KTY 84, PT100, PT 1000, PT 2000
Trip threshold resistance
User defined in parameter
F60
Reset resistance
User defined in parameter
F61
Short-circuit detection resistance
50
Ω
± 40 %
9
Analog output 1
10
Analog output 2
Terminal 9 default function
SPEED / FREQUENCY output signal
Terminal 10 default function
Motor torque producing current
Type of output
Bipolar single-ended analog voltage output
Voltage range
±10 V ± 5 %
Maximum output current
± 20 mA
Protection
20 mA max. Short circuit protection
11
0V common
Function
Common connection control terminals 1 to 11
21
0V common
Function
Common connection control terminals 21 to 31
22
+24 V User output (selectable)
Terminal 22 default function
+24 V User output
Programmability
Can be switched Off (0) or On (1) to act as a fourth digital output (positive logic only)
by setting the source
F29
and source invert
F32
Nominal output current
100 mA combined with
DIO3
Maximum output current
100 mA
200 mA total (including all Digital I/O)
Protection
Current limit and trip
23
0V common
Function
Common connection control terminals 21 to 31