Diagnostics Optimization CT MODBUS RTU Technical Data
286
E300 Design Guide
Issue Number: 1
When set to 0, a thermistor input is not selected, and
T8 Analog Input 3 Mode
(
F52
) is set to Volt or 6.
When set to 1, analog input 3 thermistor input is selected, and
T8 Analog Input 3 Mode
(
F52
) is set to Therm No Trip or 9.
T8 Analog Input 3
Thermistor Type
(
F59
)
,
T8 Analog Input 3 Thermistor Trip Threshold
(
F60
)
and
T8 Analog Input 3 Thermistor Reset Threshold
(
F61
)
are used to
configure the thermistor input.
When set to 2, the drive encoder thermistor input is selected, and
T8 Analog Input 3 Mode
(
F52
) is set to Volt or 6.
Encoder Thermistor Type
(
F69
)
,
Encoder Thermistor Trip Threshold
(
F70
)
and
Encoder Thermistor Reset Threshold
(
F71
)
are used to configure the thermistor input.
F74
Motor Thermistor Input Select
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
2
Default
Units
Type
16 Bit User Save
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RW