Diagnostics Optimization CT MODBUS RTU Technical Data
176
E300 Design Guide
Issue Number: 1
Table 7-35 UPS power control parameter
Figure 7-22 Emergency power supply backup control
Parameter
Detail
Ups Control Enable
(
O05
)
Enable, disable for UPS control
UPS Maximum Power Set point
(
O06
)
Maximum UPS power in kW. This setting prevents the UPS from being overloaded during emergency evacuation
with UPS control enable = On (1).
UPS evacuation current full load
limit
(
O07
)
Defines the percentage full load current allowed during emergency evacuation with UPS control enable = On (1)
to prevent overloading, and to extend the operating time of the UPS power supply.
UPS evacuation current no load
limit
(
O08
)
Defines the percentage no load current allowed during emergency evacuation with UPS control enable = On (1)
to prevent overloading, and to extend the operating time of the UPS power supply.
1
J58
Output power
UPS maximum
power setpoint
O06
0
Active speed
setpoint
Standard
speed
selection
0
0
Current full
load O07
Current no
load O08
B16 I-max %
DC Bus
J64
550 V
450 V
J64
DC Bus voltage
Symmetrical current
limit stored value
Symmetrical
current limit
Symmetrical
current limit
1
0
1
0
B16
UPS control
enable
UPS control
enable
O05
O05
B16
J38
1