Diagnostics Optimization CT MODBUS RTU Technical Data
300
E300 Design Guide
Issue Number: 1
Figure 8-24 Start optimizer
In Open-Loop mode this parameter is not used.
This is the start optimizer maximum speed and is set in mm / s. In Open loop start optimization applies a low speed to provide additional holding
torque prior to brake opening.
Nominal Elevator Speed
(
E01
) defines the maximum limit for this parameter.
This sets the start optimiser jerk in 10 mm / s
3
units where 1 = 10 mm / s
3
. The maximum for this parameter is limited by
Run Jerk 1
(
G13
).
This feature is helps to overcome starting stiction for elevators fitted with a motor output gearbox, or for systems fitted with guide rail pads rather than
rollers. In Open loop mode this parameter is not used.
When
Start Optimizer Enable
(
G45
) = On (1), the start optimizer is time is used during starting state 6, to time the period where
Start Optimizer Speed
(
G46
) , and
Start Optimizer Jerk
(
G47
) are used to define the start optimiser motion profile. Acceleration maximum during start optimisation is defined
by
Acceleration Rate
(
G11
).
This feature is helps to overcome starting stiction for elevators fitted with a motor output gearbox, or for systems fitted with guide rail pads rather than
rollers.
The start optimizer is always used in Open-Loop mode to provide a holding speed reference for brake release. A request to release the
brake in Open-Loop will not be made unless Start Optimizer Speed (
G46
) is reached.
G46
Start Optimizer Speed
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
10000
Default
10
Units
mm / s
Type
16 Bit User Save
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RW
G47
Start Optimizer Jerk
Mode
Open-Loop, RFC-A, RFC-S
Minimum
-VM_EX00_RUN_JERK_1
Maximum
VM_EX00_RUN_JERK_1
Default
1
Units
mm / s
3
x 10
Type
16 Bit User Save
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RW, VM, BU
G48
Start Optimizer Time
Mode
RFC-A, RFC-S
Minimum
0
Maximum
10000
Default
1000
Units
ms
Type
16 Bit User Save
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RW
Time
S
peed
G46
G47
G13
G48
NOTE