2-11 Installation & Wiring
Output Wiring (cont’d)
Figure 11—Wiring for Sourcing Transistor Outputs (See Figure 6 for Terminal Block Locations)
Model PS-6144-24-P16-M09
-
-
-
Please Note:
• Outputs are rated at 30 VDC, 50 mA.
• Transistor outputs should not be used to switch inductive devices such as solenoids or relays.
• Sourcing outputs conduct to the positive terminal of TB 11 when “on.”
Sinking/Sourcing Defined
Sinking means that when the logic is true and the output (or input device) is ON, the output (or input device)
is providing a DC common or ground to the connected device.
Sourcing means that when the logic is true and the output (or input device) is ON, the output (or input device)
is providing a +DC voltage to the connected device.
This information is important when interfacing an Electro Cam Corp. product with another electronic device. If you are using an Electro Cam Corp. product
input to an Allen-Bradley 1746-IN16 “sinking” input card* or similar A-B device, you have to supply a +DC voltage (Electro Cam Corp.
Sourcing
output)
to this card, NOT a DC common or ground. In these cases,
Sinking
is what the card does with the input voltage; sinks it to common or ground.
*Other manufacturers include, but not limited to: Koyo (formerly GE Series 1, Texas Instruments, or Siemens SIMATIC PLS’s) that use descriptions
similar to Allen-Bradley.
Содержание Plus PS-6144 Series
Страница 3: ......
Страница 4: ......
Страница 12: ...2 2 Installation Wiring Mounting Dimensions Figure 4 Mounting Dimensions ...
Страница 76: ...6 2 Communications PLµSNET II Program cont d Sample ASCII Program Copied from PS 6144 Using PLµSNET II ...
Страница 114: ......
Страница 115: ......
Страница 116: ...800 228 5487 U S A and Canada Web Site www electrocam com email ecam electrocam com PRINTED IN U S A 256 9 14 ...