2-1 Installation & Wiring
General Mounting & Wiring
C
ontroller
The controller body mounts on a DIN rail as shown in Figure 4.
Keypad/Display
Mount the keypad/display to a panel using the four studs on the back of the keyboard.
Enclosures are available from Electro Cam if an appropriate mounting location does
not exist.
DIP Switches
For convenience, set the DIP switches on the side of the controller and keypad
to their proper positions before mounting the units in a panel. See page 2-13 for
DIP switch information.
Environment
1. Allow space at both sides and the top of controller for terminal blocks to be unplugged.
2. Ambient temperature range is 0° to 55°C (32° to 130°F).
3. Locate the controller and keypad away from devices that generate electrical noise,
such as contactors and drives.
4. Use the keypad/display gasket provided to prevent contaminants from getting into
the cabinet.
Terminal Blocks
All terminal blocks can be unplugged from the controller. Each block is keyed so it cannot
be plugged into the wrong socket. All terminals are labelled on each block.
Wiring Guidelines
Follow normal wiring practices associated with the installation of electronic controls.
Some guidelines are:
1. Route input and output wiring away from high voltage, motor drive, and other high
level control signals.
2. Use shielded cables for resolver, input, transistor output, and communication circuits.
Also shield module output circuits that are driving low current electronic input circuits.
3. Ground shielded cables at the PS-6144 end
only (except for resolver cable). Use
any of the screws on the controller back for grounding.
4. Use appropriate suppression devices where module outputs are directly driving
inductive loads.
Power Supply Wiring
Connect a 20 to 30 VDC power supply to TB 8 (Fig. 5 or 6). Reversing the polarity will
blow the 1-1/4 amp power fuse. The controller will not be damaged, but you must correct
the polarity and replace the fuse before the controller will operate.
To insure electrical noise immunity, connect a good electrical ground to the ground
terminal on the power supply terminal block.
Module Mounting
A phillips head screw holds each module in place. Individual modules can be removed
and installed without affecting the other modules on the unit.
Disconnect power to the controller before changing modules.
Содержание Plus PS-6144 Series
Страница 3: ......
Страница 4: ......
Страница 12: ...2 2 Installation Wiring Mounting Dimensions Figure 4 Mounting Dimensions ...
Страница 76: ...6 2 Communications PLµSNET II Program cont d Sample ASCII Program Copied from PS 6144 Using PLµSNET II ...
Страница 114: ......
Страница 115: ......
Страница 116: ...800 228 5487 U S A and Canada Web Site www electrocam com email ecam electrocam com PRINTED IN U S A 256 9 14 ...