6-8 Communications
CMD
(hex) Name
Function
1E Grp Offset
Output group offset value.
Put:
! ADR
1E P XX YYYY CSM <CR>
Reply:
A <CR>
Get:
ADR
1E G XX CSM <CR>
Reply:
A YYYY CSM <CR>
where “XX” is the group number minus 1. “YYYY” is the offset
value for that group, in hex.
3C Shaft Offset
Shaft position offset.
Put:
! ADR
3C P XXXX CSM <CR>
Reply:
A <CR>
Get:
! ADR
3C G CSM <CR>
Reply:
A XXXX CSM <CR>
where “XXXX” is the shaft offset in hex.
1F Grp Chn Qty
Number of channels in a specified output group.
Put:
! ADR
1F P XX YY CSM <CR>
Reply:
A <CR>
Get:
! ADR
1F G XX CSM <CR>
Reply:
A YY CSM <CR>
where “XX” is the group number minus one. “YY” is the number
of output channels in that group, in hex.
21 Mode
Mode for the specified output group.
Put:
! ADR
21 P XX YY CSM <CR>
Reply:
A <CR>
Get:
! ADR
21 G XX CSM <CR>
Reply:
A YY CSM <CR>
where “XX” is the group number minus one. “YY” is the operating
mode, from zero to five.
47 Output Enab
Output Enable ANDing on or off for specified channel.
Put:
! ADR
47 P XX <00 or 01> CSM <CR>
Reply:
A <CR>
Get:
! ADR
47 G XX CSM <CR>
Reply:
A <00 or 01> CSM <CR>
where “XX” is the channel number minus one, in hex. “00” =
ANDing “off”; “01” = ANDing “on”.
4D Pgm Sel Mode
Program select terminals use Binary, Gray Code, or BCD format.
Put:
! ADR
47 P <00, 01, or 02> CSM <CR>
Reply:
A <CR>
Get:
! ADR
47 G CSM <CR>
Reply:
A <00, 01, or 02> CSM <CR>
“00” = Binary; “01” = Gray Code; “02” = BCD.
Serial Commands (cont’d)
Configuration
Commands
(cont’d)
Содержание Plus PS-6144 Series
Страница 3: ......
Страница 4: ......
Страница 12: ...2 2 Installation Wiring Mounting Dimensions Figure 4 Mounting Dimensions ...
Страница 76: ...6 2 Communications PLµSNET II Program cont d Sample ASCII Program Copied from PS 6144 Using PLµSNET II ...
Страница 114: ......
Страница 115: ......
Страница 116: ...800 228 5487 U S A and Canada Web Site www electrocam com email ecam electrocam com PRINTED IN U S A 256 9 14 ...